| Model |
1KSS60400/50400 |
| Capacity |
1KVA/700W |
| Input |
| Voltage |
120V or 220V *see note |
| Voltage Range |
120V -15%/+20% or 220V -15%/+20% |
Current
Requirement |
220V - 5.2A @ Full Load (7.8A @ Current limit) |
| 120V - 9.6A @ Full Load (14.3A @ Current limit)
|
| Frequency |
50Hz or 60Hz |
| Phase |
Single |
| Output |
| Voltage |
115V (Locked) |
| Voltage Regulation |
±1% |
| Frequency |
400Hz (50/60hz available)
|
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% at 100% linear load |
| Output Waveform |
Pure Sinewave |
| Output Current @ .7pf |
220V - 4.5A |
| 120V - 8.3A |
Non-Linear Peak
Current for 30 sec. |
220V - 6.8A |
| 120V - 12.5A |
| Power Factor |
0.9 |
| Efficiency |
| AC to AC |
>85% |
| Overload Capacity |
110% continuous,110-150% load 30 seconds, over
150% causes unit to shut down. Auto restart upon removal of
the overload. |
| Short Circuit |
Unit will cut off and must be manually restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB |
| Over Temperature |
Inverter auto cut-off when heat sink temp over
80ºC |
| Audible Alarm |
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, Input & Output voltage - frequency,
loading % |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
0-40° C; 32-104° F |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 45dB (at 1 meter) |
| Physical |
| Net Weight |
67.5lbs/30.7kg |
| Width |
7 1/8in/18.1cm |
| Depth |
16in/40.6cm |
| Height |
19 3/8in/49.3cm |
| Note: Input voltages of 208V single phase
(phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines
and 240V single phase (from a 120/20V split-phase source) -
2 hot lines are both acceptable with one hot on the input N
ternimal, and another hot on the L2 input terminal. |
Specifications subject to change without notice. |