| Size |
|
125 KVa (12.5 KVa to 300 KVa available) |
| |
| Input: |
| Voltage |
|
220/380 (or specify 240/415V or 100/200V) - 3ph |
| Frequency |
|
50 Hz (60 Hz input models also available for 50 Hz Ships) |
| Horsepower |
|
150hp (for this 125KVa unit) |
| |
| Output: |
| Voltage |
|
120/208 - 3ph |
| Frequency |
|
60 Hz (as above 50 Hz output available if specified) |
| Power |
|
125KVa, 0.8 pf, 100kW |
| |
| Physical Specs |
| Enclosure |
|
Stainless Steel |
| Dimensions |
|
70"L x 36"W x 75"H (for 125KVa unit) |
| Weight |
|
4500 lbs |
| |
| Protection |
| Input |
|
Reduced voltage motor starter, with thermal trip. |
| Output |
|
Output Circuit Breaker, Generator equipped with PMG, with overvoltage trip. |
| Overload |
|
will sustain 300% short circuit for 10 seconds to clear downstream breakers. |
| |
| Environment Tolerance |
| Temperature |
|
50º C Ambient Air |
| Wind |
|
up to 125 mph |
| Moisture |
|
Has anti-condensation heater inside motor and generator coils |